Telephone cable details

    An introduction to telephone cables

    Summary of IEC 60189-2

    Low frequency cables and wires with PVC insulation and PVC coating

    Part 2: Cables in pairs, threes, fours and fives for internal installation

    Range :
    This part of IEC 60189 applies to indoor installation cables intended to connect:
    – transmission equipment;
    – Telecommunication equipment;
    – Equipment for data processing

    1) Conductor

    Conductive material

    The conductor must be made of annealed copper, of uniform quality and free from defects.
    Copper properties should be in accordance with IEC 60028 standard.

    Conductor type
    end of the conductor
    Conductor dimensions
    Continuity of the conductor

    2) Insulation

    -Insulating materials
    The insulation should consist of polyvinyl chloride (PVC).
    Insulation thickness
    The insulation shall be continuous with as uniform a thickness as possible, minimum 0.15 mm for nominal conductor diameter up to 0.6 mm and minimum 0.25 mm for nominal conductor diameter 0.8 mm.

    3) Cabling element

    A cabling element must be
    – A pair of two insulated conductors that are twisted together and wire a and wire b are marked

    4) Packaging

    The cable core may be wrapped with a protective layer of non-wicking, non-wicking material (for example, a helical or longitudinal covering of one or more overlapping strips or a continuous thin sheath).
    If a screen is provided, the protective layer should be mandatory.

    5) Screening

    The cable core may have a screen. It must consist of copper or aluminum strip with a minimum thickness of 0.04 mm or thin strip of the same material with a minimum thickness of 0.008 mm.
    Laminated to a plastic strip.
    The tape shall be spirally wound or applied longitudinally around the wrapped core with an overlap of at least 20% or 6 mm, whichever is less.
    One or more tinned copper wires must be placed in continuous contact with the surface of the metal strip in the cable.
    The wires may be of circular or flat cross-section: the total cross-sectional area shall not be less than 0.125 mm2.
    The panel may be provided with an outer protective layer of non-wicking, non-wicking material (eg, a longitudinal or spiral wrap of one or more overlapping strips).

    6) Sheath

    -Sheath material
    The sheath should be made of polyvinyl chloride.
    -Sheath color
    The color of the sheath is preferably gray

    Summary of IEC 60708


    Low frequency cables with polyolefin insulation and moisture barrier polyolefin sheath

    Range


    This standard is intended to define polyolefin insulated cables for installation in outdoor local area networks.
    This standard applies to polyolefin insulated and moisture barrier telephone cables, filled or unfilled with copper conductors, and used as:
    a) Cables suitable for installation in channels.
    b) Cables suitable for direct burial in the ground.
    c) Cables with integrated suspension strands for aerial installations.
    This standard is in accordance with ITU-T recommendations.
    This standard includes general design details and requirements for dimensions and other construction details as well as mechanical, electrical and environmental characteristics for all types of low frequency cables with polyolefin insulation (solid or cellular), filled or unfilled, and moisture barrier polyolefin sheath. be with integrated suspension string).

    Conductive material

    The conductor must be made of annealed copper, of uniform quality and free from defects.
    Copper properties should be in accordance with IEC 60028 standard.

    Conductor type
    End of the conductor
    Conductor dimensions
    Continuity of the conductor

    2) Insulation

    -Insulating materials
    The conductor shall be covered with solid or cellular polyolefin insulation or any combination thereof. – (polyethylene or polypropylene)

    3) Cabling element

    A cabling element must be
    – A pair of two insulated conductors that are twisted together and wire a and wire b are marked

    4) Threading

    The cable elements must be converted into a number of sub-units or units that can be serially cut to produce the required number of pairs.
    – 25 pairs
    Pairs shall be identified by each insulated conductor having a color in accordance with the color scheme provided in Annex C. Each group of subunits that make up the number of 25 pairs must be marked with a common color of connections.

    5) Filling

    For filled cables, the cable core gaps must be continuously filled with a suitable compound to prevent water penetration into the cable.

    6) Core protection

    The cable core may have a protective layer (for example, a spiral or longitudinal covering of one or more strips).

    7) Sheath

    – General: The structure of aluminum multi-layer polyethylene sheath is specified for both underground cables and aerial cables. This type of sheath also offers screening.
    For aerial cables, figure “8” structure is specified.
    Circular sheath cables can also be used as aerial cables.
    – Sheath material: aluminum tape is glued to the polyethylene sheath.
    – Aluminum tape: Aluminum tape must be covered with a polymer film on at least one side. Aluminum strip without polymer layer should have a nominal thickness of at least 0.15 mm.
    – Polyethylene: Polyethylene must have at least 2.0% carbon black.

    2) dielectric strength

    The dielectric strength of the insulation should be checked on the finished cable.
    The insulation must withstand the application of d.c. Test voltage
    Test voltages for alternate durations are given in the table below.

    3) insulation resistance

    Insulation resistance at 20 degrees Celsius should not be less than:
    – For cables filled with 1 500 MOhm x km
    – or unfilled cables 5000 MOhm x km


    4) Mutual capacity

    The mutual capacitance should not exceed the values given in the table below.

    5) Capacity imbalance

    The capacitance imbalance should not exceed the values given in the following table for every 500 meters of cable length:

    *** The following parameters are not applicable for A-2Y(St)2Y cables with static plate.


    6) weakening


    The attenuation values depend on the cable design and should be provided by the manufacturer.
    Measurement method based on IEC 61156-1, 3.3.2.


    7) Near End Crosstalk (next)


    NEXT values are given in Table 6.
    Measurement method according to IEC 61156-1, 3.3.3.


    8) ELFEXT


    ELFEXT values are given in the table below.
    Measurement method based on IEC 61156-1, 3.3.5.


    9) Power sum (PS) interference loss


    The values of the total power losses of the near-end junction and the equal level at the end are given in the table below.
    Measurement method according to IEC 61156-1

    10) characteristic impedance


    The nominal value of the characteristic impedance Z0 of the cable must be in the range of 80 ohms
    130 ohms at 1 MHz, depending on design. Maximum deviation from the nominal characteristic
    Impedance should be within ± 15%.
    Measurement method based on IEC 61156-1, 3.3.6.


    11) Release speed


    The propagation speed should be more than 60% at 1 MHz.
    Measurement method according to IEC 61156-1, 3.3.1.

    Pair color coding according to IEC 60708, 60189 A-2Y

    4) Threading

    Cable elements must be converted into a number of sub-units or units that can be serially cut to produce the required number of cores, pairs or quads.